Electric Heater Batteries

We carry large stocks of Electric Heater Batteries available for speedy deliveries, we are also able to manufacture custom / bespoke sizes if required just get in touch with our sales team today.

Single Phase Electric Heater Battery

Price
£340
Shipping calculated at checkout.
Rating: 3KW

Frequently Bought Together

We Accept

American Express
Apple Pay
Diners Club
Discover
Google Pay
Maestro
Mastercard
PayPal
Shop Pay
Union Pay
Visa

Product Information

Sheathed element air duct heaters provide a clean and safe method of air heating, which is economical to install and operate, especially if an efficient control system is employed.

The heaters described here are intended for ventilation / air conditioning applications with air leaving temperatures below 60 °C

Rectangular duct heater: Flanged duct with "stab-in" type heater section to enable removal of elements without dismantling ductwork.

These heaters can be mounted in a vertical or horizontal position. Please state position when ordering so that the thermal cut-out can be selected to suit the application.

Forced air duct heater comprising sheathed electric resistance elements, mounted in a pre-galvanised steel casing.

Elements consist of a nickel/chromium resistance wire, spirally wound, insulated by compacted magnesium oxide powder and fitted within a incoloy ( AIS1321 titanium stabilised ) tube. The connection bushes of each element are1/4" BSP brass crimped on.

Elements are return bent and mounted in the terminal box with airtight brass fixing glands and insulating washers.

Heaters are designed to have an element suface temperature of 400°C at an air velocity of 2m/s.

Element tails are either fitted with saddle washers for cable connection or linked with copper busbar.

Terminal boxes are made with 1.2mm pre-galvanised steel and generally conform to IP40. 25mm conduit holes and earth stud are provided.

Every heater is fitted with a high temperature safety cut out ( manual reset ). This usually comprises a bi-metallic disc which is non-current sensitive. The switch contacts are normally closed and can withstand 13A at 240V ( this cut out should be connected into the control circuit to break the supply to the heater load ).

PLEASE REFER TO TABLE FOR ELECTRIC HEATER BATTERY RATINGS AND SIZES.

 
Reference Rating (KW) Element Quantity H W L1 L2
EHB1/3KW 5 2 280 270 125 265
EHB1/4KW 4 2 280 270 125 365
EHB1/5KW 5 2 280 270 125 465
EHB1/6KW 6 2 280 270 125 465
EHB1/7.5KW 7.5 3 280 270 125 465
EHB1/9KW 9 3 280 270 125 465



 

Protection and Fire Safety Requirements

It is recommended to have the air velocity across the elements at 2.5 m3/sec or above to prevent the elements "glowing"

Always install an airflow switch in the system to detect airflow, should the airflow fail then the heater battery needs to immediately shut down.

A Fan run on timer is recommended to allow the fan to "run on" for a minimum of two minutes which allows the heater elements to dissipate the heat. 

 

Please note these items are made to manufacture and once made we cannot accept returns for these items, Lead times for all models 2-3 weeks.

 

Three Phase Electric Heater Battery

Price
£491
Shipping calculated at checkout.
Rating: 9KW

Frequently Bought Together

We Accept

American Express
Apple Pay
Diners Club
Discover
Google Pay
Maestro
Mastercard
PayPal
Shop Pay
Union Pay
Visa

Product Information

Sheathed element air duct heaters provide a clean and safe method of air heating, which is economical to install and operate, especially if an efficient control system is employed.

The heaters described here are intended for ventilation / air conditioning applications with air leaving temperatures below 60 °C

Rectangular duct heater: Flanged duct with "stab-in" type heater section to enable removal of elements without dismantling ductwork.

These heaters can be mounted in a vertical or horizontal position. Please state position when ordering so that the thermal cut-out can be selected to suit the application.

Forced air duct heater comprising sheathed electric resistance elements, mounted in a pre-galvanised steel casing.

Elements consist of a nickel/chromium resistance wire, spirally wound, insulated by compacted magnesium oxide powder and fitted within a incoloy ( AIS1321 titanium stabilised ) tube. The connection bushes of each element are1/4" BSP brass crimped on.

Elements are return bent and mounted in the terminal box with airtight brass fixing glands and insulating washers.

Heaters are designed to have an element suface temperature of 400°C at an air velocity of 2m/s.

Element tails are either fitted with saddle washers for cable connection or linked with copper busbar.

Terminal boxes are made with 1.2mm pre-galvanised steel and generally conform to IP40. 25mm conduit holes and earth stud are provided.

Every heater is fitted with a high temperature safety cut out ( manual reset ). This usually comprises a bi-metallic disc which is non-current sensitive. The switch contacts are normally closed and can withstand 13A at 240V ( this cut out should be connected into the control circuit to break the supply to the heater load ).

PLEASE REFER TO TABLE FOR ELECTRIC HEATER BATTERY RATINGS AND SIZES.

 
Reference Rating (KW) Element Quantity H W L1 L2
EHB3/9KW 9 3 280 270 125 465
EHB3/12KW 12 6 400 270 125 370
EHB3/15KW 15 3 280 270 125 465
EHB3/18KW 18 6 400 270 125 470
EHB3/21KW 21 6 400 270 125 720
EHB3/24KW 24 6 400 270 125 720
EHB3/27KW 27 9 520 270 125 720
EHB3/30KW 30 6 400 270 125 720
EHB3/36KW 36 9 520 270 125 720
EHB3/42KW 42 12 650 270 125 720
EHB3/48KW 48 12 650 270 125 720
EHB3/54KW 54 12 650 270 125 720
EHB3/57KW 57 15 760 270 125 720
EHB3/60KW 60 12 650 270 125 720
EHB3/63KW 63 15 650 270 125 720
EHB3/69KW 69 15 650 270 125 720
EHB3/75KW 75 15 650 270 125 720
EHB3/81KW 81 21 880 270 125 720
EHB3/87KW 87 21 950 270 125 720
EHB3/90KW 90 18 880 270 125 720
EHB3/96KW 96 21 950 270 125 720
EHB3/110KW 110 24 1120 270 125 720
EHB3/120KW 120 24 1120 270 125 720



 

Protection and Fire Safety Requirements

It is recommended to have the air velocity across the elements at 2.5 m3/sec or above to prevent the elements "glowing"

Always install an airflow switch in the system to detect airflow, should the airflow fail then the heater battery needs to immediately shut down.

A Fan run on timer is recommended to allow the fan to "run on" for a minimum of two minutes which allows the heater elements to dissipate the heat. 

 Please note these items are made to manufacture and once made we cannot accept returns for these items, Lead times for all models 2-3 weeks.